Network Routers

LGR25(1000)

Intended for connection of  BACnet networks and for integration of devices of third-party vendors.


Bus: BACnet (Ethernet 10/100 Mbit/s), BACnet (arcnet 156 Kbit/s), BACnet (MS/TP 9,6-76,8 Kbit/s)
Ports: For system start-up and troubleshooting. Ïîðò RNET Supports up to four RS Standard sensors and one RS Plus, RS Pro, or RS Pro-F sensor for averaging or high/low select control. The sensors can share the Rnet port with a BACview6. For communication on EIA-232 or EIA-485. Communicates with the control module network using MS/TP (9600 bps–76.8 kbps) or a third-party device and protocol at various baud rates
Integration: 25 (LGR25) or 1000 (LGR1000) data points of third-party vendor devices can be integrated into the system.
Processor: 32-bit Motorola Power PC microprocessor with cache memory, Fast Ethernet controller, high performance 32-bit communication co-processor, ARCNET communication co-processor, and I/O expansion CAN co-processor
Memory: 16 MB non-volatile battery-backed RAM (with 12 MB available for use), 8 MB Flash memory, 32-bit memory bus
Protection: Incoming power and network connections are protected by non-replaceable internal solid-state polyswitches that reset themselves when the condition that causes a fault returns to normal. The power and network connections are also protected against voltage transient and surge events
Environmental operating range: -20 to 140°F (-29 to 60°C), 10–90% RH non-condensing

ME-LGR25(200)

Intended for handling several air handing  units, central conditioners, heating units, lighting etc. and for connection of Bacnet networks and integration of third-party equipment.


Bus: BACnet (Ethernet 10/100 Mbit/s), BACnet (arcnet 156 Kbit/s), BACnet (MS/TP 9,6-76,8 Kbit/s)
Ports: For system start-up and troubleshooting. Ïîðò RNET Supports up to four RS Standard sensors and one RS Plus, RS Pro, or RS Pro-F sensor for averaging or high/low select control. The sensors can share the Rnet port with a BACview6. For communication on EIA-232 or EIA-485.  Communicates with the control module network using MS/TP (9600 bps–76.8 kbps) or a third-party device and protocol at various baud rates
Input/Output Up to 192 phisical points can be added using 6 expansion MEX or MX
Integration: 25 (ME-LGR25) or 200 (ME-LGR200) data points of third-party vendor devices can be integrated into the system
Processor: 32-bit Motorola Power PC microprocessor with cache memory, Fast Ethernet controller, high performance 32-bit communication co-processor, ARCNET communication co-processor, and I/O expansion CAN co-processor
Memory: 16 MB non-volatile battery-backed RAM (with 12 MB available for use), 8 MB Flash memory, 32-bit memory bus
Protection: Incoming power and network connections are protected by non-replaceable internal solid-state polyswitches that reset themselves when the condition that causes a fault returns to normal. The power and network connections are also protected against voltage transient and surge events
Environmental operating range: -20 to 140°F (-29 to 60°C), 10–90% RH non-condensing

Datasheet

LGR25 CSCONNrev4.pdf
LGR1000 CSCONNrev4.pdf
ME-LGR25 CSCONNrev4.pdf
ME-LGR200 CSCONNrev4.pdf